Variable 5 – Pressure factor

TABLE 16-H—PRESSURE COEFFICIENTS (Cq)

STRUCTURE OR PART THEREOF

DESCRIPTION

Cq FACTOR

1.  Primary frames and Systems

Method 1 (Normal force method)

              Walls:

                              Windward wall

                              Leeward wall

Roofs1:

              Wind perpendicular to ridge

              Leeward roof or flat roof

              Windward roof

                              less than 2:12 (16.7%)

                              Slope 2:12 (16.7%) to less than 9:12 (75%)

                              Slope 9:12 (75%) to 12:12 (100%)

                              Slope > 12: 12 (100%)

Wind parallel to ridge and flat roofs

 

 

0.8 inward

0.5 outward

 

 

0.7 outward

 

0.7 outward

0.9 outward or 0.3 inward

0.4 inward

0.7 inward

0.7 outward

 

 

Method 2 (Projected area method)

              On vertical projected area

                              Structures 40 feet (12 192 mm) or less in height

                              Structures over 40 feet ( 12 192 mm) in height

              On horizontal projected area1

 

 

1.3 horizontal any direction

1.4 horizontal any direction

0.7 upward

2.  Elements and components not in areas of discontinuity2

Wall elements

              All structures

              Enclosed and unenclosed structures

              Partially enclosed structures

              Parapets walls

 

1.2 inward

1.2 outward

1.6 outward

1.3 inward or outward

 

Roof elements3

              Enclosed and unenclosed structures

              Slope < 7:12 (58.3%)

              Slope 7:12 (58.3%) to 12:12 (100%)

Partially enclosed structures

              Slope < 2:12 (16.7%)

              Slope 2:12 (16.7%) to 7:12 (58.3%)

              Slope > 7:12 (58.3%) to 12:12 (100%)

 

1.3 outward

1.3 outward or inward

 

 

1.7 outward

1.6 outward or 0.8 inward

1.7 outward or inward

3.  Elements and components in areas of discontinuities2'4'5

Wall corners6

Roof eaves, rakes or ridges without overhangs6

              Slope < 2:12 (16.7%)

              Slope 2:12 (16.7%) to 7:12 (58.3%)

              Slope > 7:12 (58.3%) to 12:12 (100%)

For slopes less than 2:12 (16.7%)

              Overhangs at roof eaves, rakes or ridges, and canopies

1.5 outward or 1.2 in ward

 

2.3 upward

2.6 outward

1.6 outward

 

0.5 added to values above

4.  Chimneys, tanks and solid towers

Square or rectangular

Hexagonal or octagonal

Round or elliptical

1.4 any direction

1.1 any direction

0.8 any direction

5.  Open-frame towers7'8

Square and rectangular

              Diagonal

              Normal

Triangular

 

4.0

3.6

3.2

6.  Tower accessories (such as ladders, conduit, lights and elevators)

Cylindrical members

              2 inches (51 mm) or less in diameter

              Over 2 inches (51 mm) in diameter

Flat or angular members

 

1.0

0.8

1.3

7.   Signs, flagpoles, lightpoles, minor structures8

 

1.4 any direction

1) For one story or the top story of multistory partially enclosed structures, an additional value of 0.5 shall be added to the outward Cq. The most critical combination shall be used for design. For definition of partially enclosed structures, see Section 1616.

2) Cq values listed are for 10-square-foot (0.93 m2) tributary areas. For tributary areas of 100 square feet (9.29 m2), the value of 0.3 may be subtracted from Cq, except for areas at discontinuities with slopes less than 7 units vertical in 12 units horizontal (58.3% slope) where the value of 0.8 may be subtracted from Cq. Interpolation may be used for tributary areas between 10 and 100 square feet (0.93 m2 and 9.29 m2). For tributary areas greater than 1,000 square feet (92.9 m² use primary frame values.

3) For slopes greater than 12 units vertical in 12 units horizontal (100% slope), use wall element values.

4) Local pressures shall apply over a distance from the discontinuity of 10 feet (3048 mm) or 0.1 times the least width of the structure, whichever is smaller.

5) Discontinuities at wall comers or roof ridges are defined as discontinuous breaks in the surface where the included interior angle measures 170 degrees or less.

6) Load is to be applied on either side of discontinuity but not simultaneously on both sides.

7) Wind pressures shall be applied to the total normal projected area of all elements on one face. The forces shall be assumed to act parallel to the wind direction.

8) Factors for cylindrical elements are two thirds of those for flat or angular elements.

Variable 7 – Importance factor

TABLE 16-K—OCCUPANCY CATEGORY

OCCUPANCY CATEGORY

OCCUPANCY OR FUNCTIONS OF STRUCTURE

 

IMPORTANCE FACTOR

SE1SMIC

I

SEISMIC

Ip

WIND

Iw

l.    Essential facilities2

 

Group I, Division 1 Occupancies having surgery and emergency treatment areas

Fire and police stations

Garages and shelters for emergency vehicles and emergency aircraft Structures and shelters in emergency-preparedness Centers

Aviation control towers

Structures and equipment in government communication centers and other facilities required for emergency response

Standby power-generating equipment for Category 1 facilities

Tanks or other structures containing housing or supporting water or other fire-suppression material or equipment required for the protection of Category 1, 2 or 3 structures

1.25

 

1.50

 

1.15

 

2.      Hazardous facilities

 

Group H, Divisions 1, 2, 6 and 7 Occupancies and structures therein housing or supporting toxic or explosive chemicals or substances Nonbuilding structures housing, supporting or containing quantities of toxic or explosive substances that, if contained within a building, would cause that building to be classified äs a Group H, Division 1, 2 or 7 Occupancy

 

1.25

 

1.50

 

1.15

 

3.      Special occupancy structures-1

 

Group A, Divisions 1, 2 and 2.1 Occupancies Buildings housing Group E, Divisions 1 and 3 Occupancies with a capacity greater than 300 students Buildings housing Group B Occupancies used for College or adult education with a capacity greater than 500 students Group I, Divisions 1 and 2 Occupancies with 50 or more resident incapacitated patients, but not included in Category 1 Group I, Division 3 Occupancies All structures with an occupancy greater than 5,000 persons Structures and equipment in power-generating stations, and other public utility facilities not included in Category 1 or Category 2 above, and required for continued Operation

 

1.00

 

1.00

 

1.00

 

4.      Standard occupancy structures-1

 

All structures housing Occupancies or having functions not listed in Category I, 2 or 3 and Group U Occupancy towers

 

1.00

 

1.00

 

1.00

 

5.      Miscellaneous structures

 

Group U Occupancies except for towers

 

1.00

 

1.00

 

1.00

 

1) The limitation of Ip for panel connections in Section 1633.2.4 shall be 1.0 for the entire connector.

2) Structural observation requirements are given in Section 1702.

3) For anchorage of machinery and equipment required for life-safety Systems, the value of Ip shall be taken as 1.5.

Variable 10 – Wind velocity

MINIMUM BASIC WIND SPEEDS

FIGURE 16-1—MINIMUM BASIC WIND SPEEDS IN MILES PER HOUR (x 1.61 for km/h)

Variable 33 – Seismic Factor Z

SEISMIC ZONE MAP OF THE UNITED STATES

FIGURE 16-2—SEISMIC ZONE MAP OF THE UNITED STATES For areas outside of the United States, see Appendix Chapter 16.